Article citation information:
Wheatley, G.,
Babamiri, A., Philippa, B. Vibration analysis of an Airlie beach house: a case
study in Australia. Scientific Journal of
Silesian University of Technology. Series Transport. 2022, 114, 179-192. ISSN: 0209-3324. DOI: https://doi.org/10.20858/sjsutst.2022.114.15.
Greg WHEATLEY[1], Arash BABAMIRI[2],
Bronson PHILIPPA[3]
VIBRATION ANALYSIS OF AN AIRLIE BEACH HOUSE: A CASE STUDY IN AUSTRALIA
Summary. Airlie beach
houses are quite common in the coastal areas of Australia. These houses,
similar to other buildings, provide comfort for their residents. House comfort
is not limited to temperature or sound pollution, vibration can be considered
as another equally important factor. In this article, the vibration of an
Airlie beach house was investigated. The base steel structure was modeled in
SolidWorks and Space Gass for evaluating stress distribution and nodal
displacement, respectively. To find the root cause of the distressing vibration
of the house, which was felt with dwellings, the axial acceleration of the
house’s structure was determined. Some feasible solutions such as adding
a fiber-reinforced polymer joist hanger, inserting additional rubber padding to
the joist hanger, and attaching additional bracing, were discussed and a cost
analysis was considered for the solutions. Eventually, the nature of the best
solution, which was adding rubber, was tested experimentally.
Keywords: vibration,
Airlie beach house, structure analysis
1. INTRODUCTION
Vibration prevention is crucial for structure conformity at all levels
of construction. Given the nature of small levels of vibration, minute
displacement occurs causing fatigue in components, which can significantly
reduce the lifetime of a given structure [6, 14]. It is worth noting that a
similar situation occurs with machines [10-13, 18, 23].
Over the past decade, there has been a surge in demand for buildings
that can be constructed quickly [21]. Fortunately, construction and design
techniques have enabled the structural steel sector to satisfy this demand [7]
and produce structures that are not only capable of satisfying the above
requirements, but also remain competitive in the construction market in terms
of the overall cost. This current trend of demanding larger floor areas with
lightweight designs has resulted in requiring a greater understanding of the
dynamic performance of floors subjected to environmental and human-induced
activities [1, 25].
While the modes of vibration and the physics behind vibration are quite
complex, understanding the fundamental meaning and source of vibration is
relatively easy. The most common source of vibration in moving parts are
unbalancing, which is causing the center of mass of a given object to oscillate
back and forth [22]. These minor movements, which is called vibration, may
occur due to several factors such as wind, earthquake, structural damage,
traffic vibration, and water hammer, which will be discussed in detail in the
following [9].
The effect of the air flowing through and around the house causes a
vibration because of the influx of forces being constantly applied to the
support beams. In principle, this wind vibration is exacerbated in structures
that are raised off the ground in some fashion such as houses on stilts [2]. A
cogent explanation is that the vibration has a big surface area to dissipate
over and will continue throughout the structure.
While seismic activity causes the most significant displacement [17], it
is far less common and should only be considered if the zone of construction
will experience these seismic tremors.
As vehicles such as automobiles or trains move, their weight effects can
cause waves propagation through the ground. Due to the road's speed limit,
vehicles must travel at a constant pace and vibration from each car can occur
in a regular pattern. Not only moving vehicles but also stationary automobiles
in traffic can cause vibration [16, 26], and the larger a vehicle is, the more
energy it will impart into the ground.
Another
possible cause is a water hammer occurring in the pipeline throughout the house
[8]. A water hammer occurs when a high-pressure, flowing water system is
suddenly shut off and the pressure disperses back throughout the water lines.
Most investigations have considered regular houses, however, Airlie
beach houses that are common on Australia’s coasts have not been
included. Thus, in this article, vibration analysis of a specific Airlie beach
house in Australia was studied. To find the maximum deflection of the house
structure, subfloor bracing is modeled in Space Gass, and possible solutions
for reducing the subfloor vibration was discussed. Furthermore, not only a cost
analysis comparing the solutions financially was done but also experimental
tests were conducted to evaluate the efficacy of the implied solution.
According to the uniqueness of Airlie houses' structure and their scarcity in
other parts of the world, researchers have not devoted as much attention as
required to these structures. Although there is a huge void in analyzing these
houses, this article attempted to cast light on one of the scientific aspects,
that is, vibration, of these buildings.
2. THEORY OF VIBRATION
Vibration is primarily concerned with
the relative movement of a mass. Thus, every vibration problem can be classed
as one of two different categories, namely, continuous systems, and discrete
systems [20]. Continuous systems are systems in which all the relevant mass is
directly linked together, such as a beam experiencing bending. Discrete systems
involve masses that are independent of each other, such as the horizontal
vibration of a multi-story building.
Two main characteristics of vibration
are natural frequency and acceleration. Within every physical structure, there
are natural frequencies. They are dependent on the relationship between mass
and stiffness and how they are distributed throughout the structure. The
acceleration of a vibrating system can be determined by analyzing the
displacement. Acceleration is the second differential of displacement regarding
time meaning the acceleration of a simply supported beam as a function of
position and time can be found by differentiating Eq. (1) [19].
There are multiple different methods of evaluating the acceleration of a
system. Traditionally, the most obvious method was to represent the system in
terms of the peak, or largest acceleration. However, this value does not
indicate how long the system is subjected to this level of acceleration [24].
Alternatively, the root-mean-square (RMS), acceleration can be used. The RMS
acceleration is calculated by Eq. (2).
Where T, a(t), and t stands
for the desired period, acceleration function, and time, respectively.
3. LOAD CASE SUMMARY
When
determining the response of the subfloor bracing, numerous factors have the
potential to cause vibration within the flooring. Due to the situational conditions
of the structure and the level of vibration that is expected, certain loading
scenarios have been considered.
3.1. Dead and live loads
The dead load of a structure comprises its weight, typically measured as
a uniform pressure over the entire structure. The load involves the combined
weight of the floors, walls, roof, internal supports, stairs, and any other
form of permanently fixed equipment. For a single and multi-level residential
building, a dead load of 0.75 kN/m is typically used
for design purposes as per AS 1170.1 [15].
Live loads refer to the dynamic forces that are introduced during
occupancy and intended use. They represent transient loads that are moved
throughout the structure such as the weight of people, furniture, appliances,
and other forms of moveable objects. Similar to the dead load, a standard live
load of 3.25 kN/m for a residential structure can be
obtained from AS 1170.1.
3.2. Wind loads
Wind-induced loads on the structure are the
most likely candidate for the measured floor vibration due to geographical and
climate influences on the property. Although the vibration displacement likely
exceeds the amount viable to be caused by wind, this load case summary gives
insight into the overall design of the house for its ability to disperse wind
pressure. AS 1170.2 [4] provides Eq. (3) and an estimated wind pressure acting on the windward
(North-West) side of the structure.
Where VR,
Md, Mz, Ms, and Mt
are regional wind speed, wind direction multiplier, height multiplier,
shielding multiplier, and topographic multiplier, respectively. Relevant
measurements for calculating wind loadings on the house are represented in
Table 1.
Tab. 1
Geometry features of the Airlie house
House
Geometry Characteristics |
Dimensions |
Width |
11.8 (m) |
Length |
18.5 (m) |
Height |
2.7 (m) |
Roof
Height |
1 (m) |
Roof
Angle |
3 degree |
To determine the regional wind speeds for the location of the house, the
relevant standard AS 1170.2 can be used. Assuming this
house is designed to last for an average of 60 years, an importance level of
ordinary, the relevant annual probability of exceedance is 1/500. Therefore,
for the C zone, the wind speed 𝑉𝑅 is 66 m/s following AS 1170.2.
With the same procedure, Md,
Mz, Ms, and Mt are calculated equal to 1, and
consequently, Vsit will be 66.
The force applied to the whole windward side of the house can be
averaged as Eq. (4).
In which A,
ρ, and v are the surface area, the density of the air, and wind velocity,
respectively. Therefore, the total force applied to the windward side of the
house is 267.4 kN.
To determine the distributed pressure acting across the surface area of
the subfloor bracing, this force was divided across along the length of the
structure to provide a North-West facing the pressure of 14 kN/m. In addition
to the load case developed as per AS 1170.2, a similar
wind load case developed by the original engineers of the structure was also
considered. This case was developed as per the design guidelines of AS 4055 [5]
and incorporates similar topological and geographical modifying factors. Based
on this standard, the distributed pressure across the North-West windward
surface was found to be 8 kN/m.
Although the windward side of the structure will always experience the
maximum wind-induced loading, it was decided that the South-West profile of the
structure should be considered within the load case as well. Based on the
orientation of the house, the South-West face of the structure also experiences
a substantial volume of wind as well as potential updraft due to the high
elevation above the pier footings. To account for this, the design process
outlined in AS 4055 provided a distributed pressure load of 6 kN/m. This
additional South-West load was considered for both load cases.
4. MODEL DEVELOPMENT
With two wind-induced load cases developed, a suitable model is required
to accurately represent the floor response and the effectiveness of the
subfloor bracing. Based on the original floor plan details and photos of the
property provided by the homeowner, a structural model of the subfloor bracing
was developed in Space Gass before any construction (Figure 1).
Fig. 1. Space gass model
of subfloor bracing
The scope of the project was decided to be limited to only consider the
steelwork from the top of the pier footings up to the timber floor beams and
joists. This decision was made to simplify the analysis process as it is likely
that critical levels of vibration exist within this region. Sections of the
property that were removed to simplify the model include the front entry
balcony, external stairway, and all structural components that exist above the
floor beams.
The subfloor bracing consists of steel square hollow section (SHS)
columns that are bolted to the tops of the pier footings and the bottom flange
of the steel bearers. The timber floor beams are bolted to and run
perpendicular to these bearers and are the main structural support for the
joists. The larger SHS columns are strutted together with circular hollow
section (CHS) members and then all connected nodes are braced with threaded
rods. For sections where no CHS members strut between columns, equal angle EA
members are fixed back to back at the corners of the columns. With the critical
components of the structure modeled, the load cases can be applied (Figures 2
and 3).
Non-linear static analysis was used to determine nodal displacement
values at locations where structural members are connected. The displacement
values at every node were then analyzed to determine the location of the
greatest vertical displacement (Figure 4).
Fig. 2. AS 4055-2012
case with live and dead loads
Fig. 3. AS 1170.2-2002 case with live and dead loads
Additionally, to measure stress distribution in the beam members, they
were modeled in SolidWorks and the results are presented in Figure 5 and 5. As
seen in Figure 5, the house is largely suspended off the ground but does have a
large roughly six by six by a three-meter concrete slab in the back corner. The
slab should be causing a large amount of rigidity to the immediate structure if
mounted securely since any vibration near the slab will need to move the slab
itself or the house would start being damaged in that area. Figure 6 shows a
simulation of the bending and axial stress in all the steel members of the
house. The estimated max stress found in the bearers is 150 MPa, which is well
under the 360 MPa standard AS/NZS 3679.1-350 [3].
Fig. 4. AS 1170.2 load case nodal displacements
Fig. 5. SolidWorks model
of the house
Fig. 6. Axial and
bending stress distribution in the structure
5. DESIGN AUDIT
The following design audit is to analyze the house
located at Lot 72 Kingfisher Terrace, Jubilee Pocket (Figure 7). On any
building, the wind will cause a natural vibration, such vibration will be
almost unnoticeable to people. Such vibration is considered background and
contributes to the random noise measuring equipment will detect. When comparing
standard wind loading graphs to the measured acceleration data, some
similarities explain the noise present in the data.
As seen in Figures 8 and 9, the house experiences an
illogical amount of vibration relative to the conditions subject to the house.
There are no nearby trains passing by, no excessive wind could cause this level
of vibration, and damage is not detected either.
Fig. 7. The
finished design of the Airlie house
Fig. 8.
Axial acceleration of the structure
Fig. 9.
Estimated displacement
Further analysis is needed to determine the root cause;
however, based on the studies done in this report, the house design is valid
and does not need any structural changes as it is up to standards.
5.1. Solution
The first solution is to counter the most sag found in the house's floor
supports. The bracing will go between the supports on either side of this
point. By adding additional bracing, the rigidity of the structure may lessen
any vibrations or reduce their effect. If the vibration cannot be prevented by
an increase in rigidity, then the additional bracing will have practically no
effect. The bracing will be a copy of the existing bracing designs on the house
to maintain conformity, corresponding to the equal angle bracing in fab
drawings.
The other solution is to replace the current joist hangers with a
fiber-reinforced polymer variant. The polymer nature of the hangers will allow
any vibrations to be absorbed and lessened at the base of the floor. The
polymer joist hangers could also have additional rubber padding added to the
platform where the joists rest as seen in Figure 10. This solution will work if
the vibrations are passing through the supports into the floor or they are
transferring through the floors. If the vibrations are caused above the joists,
then the hangers will have a lessened effect.
Fig. 10.
Fiber-reinforced polymer joist hanger
5.2. Experimental testing
The physical testing was conducted via a vibrational motor acting on a
steel plate. A strain gauge was placed on the steel and recordings were taken
of the strain over time. This process was then repeated for the case where
rubber acted between the steel and the motor. The setup of the experiment can
be seen in Figure 11.
Fig. 11. Experimental
setup
The results of this experiment are shown in Figure 11. The strain
without the rubber glanced from the positive into the negative. The case with
the rubber, however, showed a constant positive strain, proving that the rubber
reduced the extent to which the steel moved.
To quantify these results, the factor by which the rubber had reduced
the movement in the steel must be determined. To do this, the ratio by which
the change in strain occurs must be produced. This will give an accurate idea
of how the rubber effects the changes in the steel.
Taking the change in strain, the average of the ratio between these
changes will give a rough idea of how much the rubber reduces the changes in
strain by a ratio.
Fig. 11. Physical
testing results
From these ratios, the rubber was determined to reduce the change in
strain by 4.55x. This should be proportional to the
overall displacement as strain is merely a measurement of elongation. Although
this is not as accurate, it shows a rough idea of the level of vibration
reduction. If we take the initial value of 30 mm of displacement and aim to
reduce it to below 1 mm of displacement.
Therefore, the vibration needs to be reduced by a factor of 33.333 times to reach below 1 mm. Taking the amount by which
the rubber reduces vibration and dividing by this value will give the rough
rubber thickness required. That is, 7.326 times the
thickness of 5 mm gives 36.63 mm. Thus, 36.63 mm of rubber is required to reduce the vibration assuming
ideal conditions and rubber strain reduction is linear. The recommended amount
of rubber is 40 as the original value of 36.63 mm will
be rounded up to add a level of vibration reduction.
5.3. Cost analysis
A summary of the cost analysis for the proposed solution is represented
in Table 2. The solutions are divided between a low cost or high cost. The
additional bracing solution would be low cost with a replication of current
bracing in the suggested area. The cost of materials would be approximately $50,
and the cost of labor would be between $100 and $200.
The alternate solution of replacing the steel joist hangers with
fiber-reinforced polymer joist hangers would cost substantially more. The
materials would cost $220, and the labor costs could easily exceed $1000 with
the need for specific equipment to support the roof given the awkward position
of the joists making it harder to install.
Tab. 2.
Cost analysis
Item |
Type |
Dimensions |
Material
Cost |
Quantity |
Total
Unit |
Total
Cost |
Galvanized Steel Column |
SHS |
150x 4 mm |
$50/m |
6 |
29.1 m |
$1455 |
SHS |
100x 4 mm |
$40/m |
6 |
22.5 m |
$900 |
|
SHS |
75x4 mm |
$28/m |
2 |
6.3 m |
$176 |
|
F14 HWD |
Post |
75x75 mm |
$20/m |
2 |
3.2 m |
$64 |
Concrete |
Square Footing |
1.5x1.5x 1.5 m |
$250/m3 |
12 |
38.5 m3 |
$9610 |
Pier Footing |
0.45x 1.2 m |
$250/m3 |
2 |
0.38 m3 |
$95 |
|
Pier Footing |
0.6x 1.2 m |
$250/m3 |
2 |
0.68 m3 |
$170 |
|
Slab |
6.36 x 6.19x0.1 m |
$250/m3 |
1 |
3.94 m3 |
$984 |
|
Bracing |
Equal Angle |
75x75x6 mm |
$20/m |
6 |
46.9 m |
$938 |
Rod |
Φ16 mm |
$4/m |
2 |
11.2 m |
$44.8 |
|
Rod |
Φ 12 mm |
$3/m |
8 |
45.6 m |
$136 |
6. CONCLUSIONS
Vibration is an important factor when house comfort is considered. In
this article, an Airlie beach house in Australia was evaluated from a vibration
point of view since the dowelling reported an uncomfortable vibration. The
results of this report show that the data presented was more than what was
expected due to various factors. The project was broken down into three
components; determining the cause, conducting an audit on the house, and
finally coming up with a solution to reduce the vibration. Although many factors
were considered, the most likely cause expected would be a live loading with a
wind load added on. The results from the audit show that the design of the
house was acceptable and that everything was up to standard in that regard.
Finally, multiple solutions were made, depending on cost, etc. An experimental
test was carried out with the aid of a vibrational motor operating on a steel
plate. The outcomes of the experiment revealed that adding a rubber can reduce
the vibration of the connected steel to the vibrational motor. While there is
no conclusive way to find out if this will solve the vibration of the house, it
is believed that the solutions should reduce the vibration by some factors;
however, given the limited scope of the project further testing and
investigation is required.
References
1.
Abd Ghafar N.H., Shamsul
Kamar I.Z., David Yeoh E.C., Koh H.B. 2020. ,,Walking Induced Floor Vibration
on Glulam Timber Floor”. Lecture Notes in Civil Engineering: 1605-1611.
2.
Amoroso Samuel D., Levitan
Marc L. 2011. ,,Wind loads for high-solidity open-frame structures”. Wind
and Structures 14(1): 1-14.
3.
Australian / New Zealand
Standard TM: Australian / New Zealand Standard TM
Structural steel Part 1 : Hot-rolled bars and sections. 1996 (2010). P.
42.
4.
Australian Standard: AS/NZS 1170.2: Standards Australia,
2011.
ISBN: 978-7337 9805-4.
5.
Australian Standard:
Australian Standard AS 4055-2012, Wind loads for housing (2013), No May 2011.
P. 9722.
6.
Beards Chris. 1996. Structural
vibration: analysis and damping.Elsevier. ISBN: 0080518052.
7.
Bjorhovde Reidar. 2004.
,,Development and use of high performance steel”. Journal of
Constructional Steel Research 60(3): 393-400.
8.
Cao Yinping, Dou Yihua,
Huang Yuxi, Cheng Jiarui. 2019. „Study on Vibration Characteristics of
Fracturing Piping in Pump-Starting and Pump-Stopping Water Hammer”. Journal
of Failure Analysis and Prevention 19(4): 1093-1104. Springer.
9.
Chik T.N.T., P.C. Xian, N.A.
Yusoff. 2020. „Vibration Criteria Analysis on Floor due to Human
Walking” IOP Conference Series: Materials Science and Engineering
713: 12046. IOP Publishing.
10.
Czech Piotr. 2011. „An
intelligent approach to wear of piston-cylinder assembly diagnosis based on
entropy of wavelet packet and probabilistic neural networks”.
Communications in Computer and Information Science 239: 102-109. DOI: https://doi.org/10.1007/978-3-642-24660-9_12.
Springer, Berlin, Heidelberg. ISBN: 978-3-642-24659-3. ISSN: 1865-0929. In:
Mikulski Jerzy (eds), Modern transport telematics, 11th International
Conference on Transport Systems Telematics, Katowice Ustron, Poland, October
19-22, 2011.
11.
Czech Piotr. 2013.
„Diagnose car engine exhaust system damage using bispectral analysis and
radial basic function”. Advances in Intelligent Systems Research 30:
312-315. DOI: https://doi.org/10.2991/iccnce.2013.78. Atlantis Press.
ISBN: 978-90-78677-67-3. ISSN: 1951-6851. In: Zheng D., Shi J., Zhang L. (eds),
Proceedings of the International Conference on Computer, Networks and
Communication Engineering (ICCNCE), Beijing, China, May 23-24, 2013.
12.
Czech Piotr. 2013.
„Diagnosing a car engine fuel injectors' damage”. Communications in
Computer and Information Science 395: 243-250. DOI: https://doi.org/10.1007/978-3-642-41647-7_30.
Springer, Berlin, Heidelberg. ISBN: 978-3-642-41646-0; 978-3-642-41647-7. ISSN:
1865-0929. In: Mikulski Jerzy (eds), Activities of transport telematics, 13th
International Conference on Transport Systems Telematics, Katowice Ustron,
Poland, October 23-26, 2013.
13.
Graževičiūtė
J., I. Skiedraitė, V. Jūrėnas, A. Bubulis, V.
Ostaševičius. 2008. „Applications of high frequency vibrations
for surface milling”. Mechanika
1: 46-49.
14.
Lin Weiwei, Teruhiko Yoda.
2017. Bridge Engineering: Classifications, Design Loading, and Analysis
Methods. Oxford: Butterworth-Heinemann. P. 245-271.
15.
Loading S A A, Part Code.
1989. Australian Standard® SAA Loading Code Part 2: Wind loads.
P. 1-99.
16.
Morbia Hardik B., Sanghvi
Capt. C.S., Bhavani Himesh K. 2011. „Effect of Road Traffic Vibration on
Historic Structures”. Indian Journal of Applied Research 3(5):
318-320.
17.
Muñoz Andre, Miguel
Diaz, Roy Reyna. 2019. „Applicability study of a low cost seismic
isolator prototype using recycled rubber”. IEEE Transactions on
Evolutionary Computation 29(2).
18.
Ostaševičius V.,
V. Jurėnas, M. Žukauskas. 2014. „Investigation of energy
harvesting from high frequency cutting tool vibrations”. Mechanika 5: 500-505.
19.
Shabana Ahmed A. 1991. Theory
of Vibration. Springer.
20.
Smith Andrew L., Stephen J.
Hicks, Paul J. Devine. 2007. Design of floors for vibration: A new approach”.
Steel Construction Institute Ascot, Berkshire, UK. ISBN: 1859421768.
21.
Szolomicki Jerzy, Hanna
Golasz-Szolomicka. 2019. „Technological Advances and Trends in Modern
High-Rise Buildings”. Buildings 9(9). ISBN: 2075-5309.
22.
Thomson William. 2018. Theory
of vibration with applications. CrC Press. ISBN: 1351408496.
23.
Ubartas M., V.
Ostaševičius, S. Samper, V. Jūrėnas, R.
Daukševičius. 2011. „Experimental investigation of vibrational
drilling”. Mechanika 4:
368-373.
24.
Vibration
Guidelines used in Australia - Telemetrix. Available at:
http://www.telemetrix.com.au/vibration-guidelines-used-in-australia/. -
abgerufen am 2021-02-17.
25.
Wang Shu, Mingzhu Wang,
Guojun Zhang, Jiaqi Ge, Jiyang Huang, Qiming Zhang, Youheng Duan, Xuechun Liu.
2012. „Study on static and seismic performance of multi-floor steel
cantilevered structure”. Journal of Building Structures 33(4):
77-89.
26.
Zhang Zhiqiang, Ma Fei,
Zhang Bill. 2018. „Vibration measurement of long-span floors in
high-speed railway station”. Journal of Vibroengineering 20(7):
2705-2719. JVE International Ltd.
Received 01.10.2021; accepted in
revised form 26.11.2021
Scientific Journal of Silesian University of Technology. Series
Transport is licensed under a Creative Commons Attribution 4.0
International License
[1] Department of Science & Engineering,
Faculty of Mechanical
Engineering, James Cook University, Bebegu Yumba Campus, Townsville QLD 4811,
Australia. Email: greg.wheatley@jcu.edu.au. ORCID: https://orcid.org/0000-0001-9416-3908
[2]
Department of Engineering, Faculty of Mechanical Engineering, University of
Kurdistan, Kurdistan, Iran. Email: arash.babamiri71@gmail.com.
ORCID: https://orcid.org/0000-0002-3094-3259
[3] Department of Science & Engineering, Electronic Systems and IoT Engineering, James Cook University, Cairns QLD, Australia. Email: bronson.philippa@jcu.edu.au. ORCID: https://orcid.org/0000-0002-5736-0336